SPIRAX SARCO · STEAM SYSTEM ACCESSORIES
Spirax Sarco AV13 Thermostatic Air Vent for Steam Systems
Spirax Sarco AV13 balanced pressure thermostatic air vent for steam systems. PN16 rated, brass body, BSP/NPT connections. Available at PC Engineering
Overview
The Spirax Sarco AV13 is a maintainable balanced pressure thermostatic air vent designed specifically for steam systems. It features angled connections and a robust brass body construction suitable for industrial steam applications.
This air vent operates on the thermostatic principle, using a stainless steel capsule that responds to temperature differences between air and steam. When air or other non-condensable gases accumulate in the steam system, the AV13 automatically vents them to atmosphere, ensuring efficient heat transfer and preventing corrosion caused by trapped air.
The AV13 is designed for installation at high points in steam mains and equipment where air naturally collects. It complies fully with the European Pressure Equipment Directive 97/23/EC and is available with manufacturer's Typical Test Reports for documentation requirements.
Key Features
- Balanced pressure thermostatic operation for reliable air venting
- Maintainable design with replaceable capsule and seat assembly
- Brass body construction (BS EN 12165 CW 617N) for corrosion resistance
- Stainless steel internals including capsule, spring, and seat
- Angled connections for flexible installation
- Available in BSP (parallel) or NPT thread options
- PN16 body design rating
- Cold Kv value of 0.45
Specifications
| Parameter | Value | |||||
|---|---|---|---|---|---|---|
| Sizes Available | ⅜", ½", ¾" | |||||
| Pipe Connections | Screwed BSP (BS 21 parallel) or NPT | |||||
| Body Design Rating | PN16 | |||||
| Maximum Allowable Pressure (PMA) | 16 bar g @ 120°C | |||||
| Maximum Allowable Temperature (TMA) | 250°C @ 7 bar g | |||||
| Maximum Operating Pressure (PMO) | 13 bar g @ 220°C | |||||
| Maximum Operating Temperature (TMO) | 250°C @ 7 bar g | |||||
| Minimum Operating Temperature | 0°C | |||||
| Cold Hydraulic Test Pressure | 24 bar g | |||||
| Kv Value (Cold) | 0.45 | |||||
| Body Material | Brass BS EN 12165 CW 617N | |||||
| Capsule Material | Stainless Steel | |||||
| Seat Material | Stainless Steel BS 970 431 S29 | |||||
| O-Ring Material | Synthetic rubber high fluorine fluorocarbon | |||||
| Size | A (mm) | B (mm) | C (mm) | D (mm) | E (mm) | Weight (kg) |
| ⅜" | 18 | 32 | 49 | 25 | 55 | 0.40 |
| ½" | 20 | 38 | 53 | 25 | 55 | 0.40 |
| ¾" | 27 | 40 | 62 | 25 | 55 | 0.45 |
Applications
The Spirax Sarco AV13 air vent is used across various industrial steam applications:
- Steam mains and distribution headers — Installed at high points to vent accumulated air during system startup and operation - Heat exchangers and process equipment — Removes air pockets that reduce heat transfer efficiency - Steam tracing systems — Ensures complete steam filling of tracing lines - Sterilizers and autoclaves — Critical for removing air to achieve proper sterilization temperatures - Jacketed vessels — Maintains efficient heating by eliminating air locks
Industries served include pharmaceuticals, food processing, textiles, refineries, chemical plants, and any facility operating steam-based heating or process systems.
Frequently Asked Questions
Get a Quote
Contact PC Engineering for pricing, availability, and technical support for the Spirax Sarco AV13 Air Vent. Call us or fill in our inquiry form — our engineers will respond within 24 hours.
More from Spirax Sarco
- Spirax Sarco AVC32 Carbon Steel Thermostatic Air Vent for Steam Systems
- Spirax Sarco BPC32 & BPC32Y Carbon Steel Balanced Pressure Thermostatic Steam Traps
- BPT13 Brass Balanced Pressure Thermostatic Steam Trap - Spirax Sarco
- Spirax Sarco BRV2S SG Iron Pressure Reducing Valve – Direct Acting PRV for Steam & Compressed Air
- Spirax Sarco BSA Bellows Sealed Isolation Valves – Zero Emission Globe Valves for Steam Systems
- Spirax Sarco BSA3T Bellows Sealed Stop Valve – Throttling Isolation Valve for Steam & Condensate
Related Steam System Accessories
Brand
Find the losses before you invest in new equipment.
Steam and pump system walkthroughs that identify inefficiencies, energy losses and improvement priorities before any new product is specified.