SPIRAX SARCO · AIR VENTS
Spirax Sarco AE50S Automatic Air and Gas Vent for Liquid Systems
Spirax Sarco AE50S stainless steel automatic air vent for liquid systems. Ideal for removing air/gas in industrial piping. Available at PC Engineering
Overview
The Spirax Sarco AE50S is an automatic air and gas vent engineered specifically for liquid systems in industrial applications. This float-operated vent automatically releases accumulated air and non-condensable gases from pipelines, maintaining system efficiency and preventing air-locking issues in process lines.
Constructed with a fully welded 304L austenitic stainless steel body, the AE50S offers excellent corrosion resistance suitable for demanding process environments. The unit is designed for maintenance-free operation with no user-serviceable parts, reducing downtime and maintenance costs. It complies with the European Pressure Equipment Directive 2014/68/EU and comes standard with EN 10204 3.1 material certification for the bowl, cover, and inlet connection.
The AE50S is suitable for high-pressure liquid systems up to 41.4 bar g and can handle operating temperatures ranging from -60°C to 427°C, making it appropriate for a wide range of industrial liquid handling applications including superheated water systems.
Key Features
- Fully welded 304L austenitic stainless steel construction for corrosion resistance
- Automatic float-operated venting mechanism — no manual intervention required
- Maintenance-free, sealed design with no spare parts needed
- High-pressure capability up to 41.4 bar g (600 psi g)
- Wide temperature range: -60°C to 427°C
- CE marked, compliant with PED 2014/68/EU
- EN 10204 3.1 material certification included as standard
- Suitable for liquids with minimum specific gravity of 0.65
Specifications
| Parameter | Value |
|---|---|
| Inlet Connection | ¾" female BSP Rp (ISO 7-1) or NPT |
| Outlet Connection | ½" female BSP Rp (ISO 7-1) or NPT |
| Body Design Rating | ANSI 300 |
| Maximum Allowable Pressure (PMA) | 41.4 bar g @ 30°C (600 psi g @ 86°F) |
| Maximum Allowable Temperature (TMA) | 427°C (801°F) |
| Minimum Allowable Temperature | -254°C (-425°F) |
| Maximum Operating Pressure (PMO) | 41.4 bar g @ 30°C (600 psi g @ 86°F) |
| Maximum Operating Temperature (TMO) | 427°C @ 23.6 bar g (801°F @ 342 psi g) |
| Minimum Operating Temperature | -60°C (-76°F) |
| Maximum Differential Pressure (PMX) | 30 bar g (435 psi g) |
| Max Cold Hydraulic Test Pressure | 63 bar g (914 psi g) |
| Minimum Specific Gravity | 0.65 |
| Body Material | Austenitic stainless steel ASTM A240 304L |
| Float Material | Austenitic stainless steel AISI 316L |
| Dimensions (A × B × C) | 175 mm × 79 mm × 18.5 mm |
| Weight | 1 kg (2.20 lbs) |
Applications
The Spirax Sarco AE50S automatic air vent is used across various industrial sectors where air and gas removal from liquid systems is critical:
- Power plants — boiler feedwater systems, condensate lines - Chemical processing — process liquid pipelines, heat exchanger circuits - Pharmaceutical manufacturing — purified water and WFI systems - Food and beverage — CIP systems, process water lines - HVAC and building services — chilled water and hot water circuits - Oil and gas — liquid hydrocarbon transfer lines - Superheated water systems — with recommended inlet piping configuration
Frequently Asked Questions
Get a Quote
Contact PC Engineering for pricing, availability, and technical support for the Spirax Sarco AE50S Automatic Air and Gas Vent. Call us or fill in our inquiry form — our engineers will respond within 24 hours.
More from Spirax Sarco
- Spirax Sarco AEL6 Series Smart Electric Actuators for Control Valves DN15–DN100
- Spirax Sarco APT10-4.5 Automatic Pump Trap – Steam Operated Condensate Removal
- Spirax Sarco APT10, APT14 & APT14HC-PPU Automatic Pump-Trap Packaged Units
- Spirax Sarco APT14 Automatic Pump Trap – Steam-Powered Condensate Removal for Vacuum & Pressure Applications
- Spirax Sarco AV13 Thermostatic Air Vent for Steam Systems
- Spirax Sarco AVC32 Carbon Steel Thermostatic Air Vent for Steam Systems
Related Air Vents
Brand
Find the losses before you invest in new equipment.
Steam and pump system walkthroughs that identify inefficiencies, energy losses and improvement priorities before any new product is specified.